genlp
genloop

50 Hz and 60 Hz by Country

Which countries run their grids at 50 Hz and which at 60 Hz, and what that means for a turbine, a generator or a whole plant that has to move between them.

01 · By region

Sixty in most of the Americas, fifty almost everywhere else.

Most of the Americas run at 60 Hz, along with a handful of countries elsewhere. The rest of the world runs at 50 Hz.

Region60 Hz50 Hz
North AmericaUnited States, Canada, Mexico, BermudaGreenland
Central AmericaBelize, Costa Rica, El Salvador, Guatemala, Honduras, Nicaragua, PanamaNone
CaribbeanAntigua and Barbuda, Bahamas, Cuba, Dominican Republic, Haiti, Saint Kitts and Nevis, Trinidad and Tobago; and the territories of Anguilla, Aruba, the British Virgin Islands, the Cayman Islands, Montserrat, Puerto Rico, Sint Maarten and the US Virgin IslandsBarbados, Dominica, Grenada, Jamaica, Saint Lucia, Saint Vincent and the Grenadines; and Bonaire, Curaçao, Guadeloupe and Martinique
South AmericaBrazil, Colombia, Ecuador, Guyana, Peru, Suriname, VenezuelaArgentina, Bolivia, Chile, Paraguay, Uruguay, French Guiana
EuropeNoneEvery country
AfricaSee the note on LiberiaEvery other country
Middle EastSaudi ArabiaEvery other country
AsiaSouth Korea, Taiwan, the Philippines, and western JapanEvery other country, including China, India and eastern Japan
Oceania and the PacificAmerican Samoa, French Polynesia, Guam, PalauAustralia, New Zealand and most other island states

Mains frequency as published in public tables of national standards, checked in October 2026. Liberia appears at 60 Hz in some tables and 50 Hz in others. An island or an industrial site can differ from its country, so confirm the frequency at the point of connection before specifying a machine.

02 · Why it matters

Frequency is set by the machine.

A grid’s frequency is the speed of every generator on it. That is why it is the first line of a requirement and the first line of a data sheet.

3,000 or 3,600 rpm

A two-pole generator makes 50 Hz at 3,000 rpm and 60 Hz at 3,600 rpm. A turbine coupled straight to it is designed around that speed.

Direct-drive frames are fixed

The GE 7EA and 7FA and the Siemens 501D5 and 501F are 60 Hz machines. The GE 9E and 9FA and the Siemens V94.2 are 50 Hz machines. None can be economically converted.

Geared and aeroderivative units

The GE Frame 5 and Frame 6B drive their generators through a gearbox, and the Alstom GT11N2 does for 50 Hz. The GE LM2500, TM2500 and LM6000 are offered for both grids. A unit is still built for one frequency, so the package has to match.

The rest of the plant

Generators, transformers and motors are built for one frequency as well. Moving a plant between grids means checking each of them, not only the turbine.

03 · Frames by grid

Where each frame can go.

The gas turbine frames Genloop is asked about most, sorted by the grid they serve.

GridFramesMarkets
60 Hz onlyGE 7EA, Siemens 501D5, Siemens 501F, GE 7FANorth and Central America, Brazil and the north and west of South America, Saudi Arabia, South Korea, Taiwan, the Philippines, western Japan
50 Hz onlyGE 9E, Siemens V94.2, GE 9FAEurope, Africa, most of Asia and the Middle East, Australia, and Argentina, Bolivia, Chile, Paraguay and Uruguay
Either gridGE Frame 5, GE Frame 6B, Alstom GT11N2, GE LM2500 and TM2500, GE LM6000Anywhere, once the package matches the grid

Each frame’s output and speed are in the frame comparison. Genloop’s 50 Hz holdings are on one page, and the register gives the frequency of every unit.

04 · Questions

What people ask about frequency.

Short answers, for a first conversation about a unit that has to cross a border.

Which countries use 60 Hz?

The United States, Canada, Mexico, all of Central America and much of the Caribbean. In South America: Brazil, Colombia, Ecuador, Guyana, Peru, Suriname and Venezuela. Outside the Americas: Saudi Arabia, South Korea, Taiwan, the Philippines and western Japan.

Which countries use 50 Hz?

Almost everywhere else: all of Europe, nearly all of Africa, the Middle East apart from Saudi Arabia, most of Asia including China and India, Australia and New Zealand, and in South America Argentina, Bolivia, Chile, Paraguay and Uruguay.

Does Japan use 50 Hz or 60 Hz?

Both. Eastern Japan, including Tokyo, Yokohama, Sendai and Sapporo, runs at 50 Hz. Western Japan, including Osaka, Kyoto, Nagoya and Hiroshima, runs at 60 Hz. Frequency converter stations join the two halves.

Can a 60 Hz gas turbine run on a 50 Hz grid?

Not a direct-drive heavy frame. Its compressor and turbine are designed for 3,600 rpm, and a 50 Hz generator needs 3,000 rpm. A geared frame such as the GE 6B can be converted, because the change is made at the gearbox, and aeroderivative packages are built for either grid. For a 50 Hz project the practical answer is a machine built for 50 Hz.

Why does grid frequency matter when buying or selling used power equipment?

It decides where a machine can go. A direct-drive 60 Hz frame can only be placed in a 60 Hz country, and the same holds at 50 Hz. Frequency is the first thing a buyer checks, and one of the first things that sets the market for a used unit.

Investment recovery runs in two directions.

For owners
Sell Equipment→